A15-MAINTENANCE REQUESTED ALARM RESETING article

MAINTENANCE INTERVAL

  • Each time the engine is started, the hour counter for the operating minutes for the maintenance requested interval of the generating set, expressed in minutes, is activated.
  • Alarm code "A15" (Maintenance request) is displayed and the audible alarm output is energised when the generating set reaches the programmed operating hours for the maintenance requested interval.
  • In presence of this alarm, the generating set can continue to normally operate but at each new starting the audible alarm output is energised.
  • After having carried out the necessary maintenance of the generating set, alarm reset is conducted by placing th unit in OFF mode and pressing the OFF and MAN keys simultaneously for 5 seconds. "A15" alarm indication disappears from the display  and the hour counter of maintenance requested interval is zeroed.
  • The hour counter of maintenance requested interval can also be zeroed in absence of "A15" alarm.
  • The unit keeps the operating time of the generating set stored for the maintenance requested interval.